6 Set up with the display and adjustment module PLICSCOM

VEGASON 63 • 4 … 20 mA/HART - two-wire

28777-EN-130417

with [+] and save with [OK]. The cursor jumps now to the distance

value.

2. Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. Keep in mind that the max.

level must lie below the dead band.

3. Save the settings with [OK] and move to "Medium selection" with

[->].

Each product has different reflective properties. In addition, there

are various interfering factors which have to be taken into account:

agitated product surfaces and foam generation (with liquids); dust

generation, material cones and echoes from the vessel wall (with

solids). To adapt the sensor to these different conditions, you should

first select "Liquid" or "Solid".

Medium

Liquid

With solids, you can also choose between "Powder/Dust", "Granular/

Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted perfectly to

the product and measurement reliability, particularly in products with

poor reflective properties, is considerably increased.
Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

Apart from the medium, the vessel shape can also influence the

measurement. To adapt the sensor to these measuring conditions,

this menu item offers different options depending on whether liquid

or bulk solid is selected. With "Liquids" these are "Storage tank",

"Stilling tube", "Open vessel" or "Stirred vessel", with "Solid", "Silo" or

"Bunker".

Vessel form

Storage tank

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

To suppress fluctuations in the measured value display, e. g. caused

by an agitated product surface, a damping can be set. This time can

be between 0 and 999 seconds. Keep in mind that the reaction time of

the entire measurement will then be longer and the sensor will react

to measured value changes with a delay. In general, a period of a few

seconds is sufficient to smooth the measured value display.

Damping

0 s

Medium selection

Vessel form

Damping