6 Set up with the display and adjustment module PLICSCOM

VEGASON 63 • 4 … 20 mA/HART - two-wire

28777-EN-130417

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A linearisation is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. in a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearisation curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. By activating the appropriate curve, the

volume percentage of the vessel is displayed correctly. If the volume

should not be displayed in percent but e.g. in l or kg, a scaling can be

also set in the menu item "Display".

Linearization curve

Linear

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

In this menu item you can enter an unambiguous designation for the

sensor, e.g. the measurement loop name or the tank or product des-

ignation. In digital systems and in the documentation of larger plants,

a singular designation should be entered for exact identification of

individual measuring points.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you can

now jump to the main menu with the [ESC] key.

High sockets or vessel installations, such as e. g. struts or agitators as

well as buildup and weld joints on the vessel walls, cause interfering

reflections which can impair the measurement. A false echo storage

detects and marks these false echoes, so that they are no longer

taken into account for the level measurement. A false echo memory

should be created with low level so that all potential interfering reflec-

tions can be detected.

False signal suppression

Change now?

Proceed as follows:
1. Move from the measured value display to the main menu by

pushing [OK].

2. Select the menu item "Service" with [->] and confirm with [OK].

Now the menu item "False signal suppression" is displayed.

Linearization curve

Sensor-TAG

False signal suppression