6 Set up with the display and adjustment module PLICSCOM
VEGASON 63 • 4 … 20 mA/HART - two-wire
28777-EN-130417
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
A linearisation is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. in a horizontal cylindri-
cal or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed for
these vessels. They represent the correlation between the level per-
centage and vessel volume. By activating the appropriate curve, the
volume percentage of the vessel is displayed correctly. If the volume
should not be displayed in percent but e.g. in l or kg, a scaling can be
also set in the menu item "Display".
Linearization curve
Linear
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product des-
ignation. In digital systems and in the documentation of larger plants,
a singular designation should be entered for exact identification of
individual measuring points.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is finished and you can
now jump to the main menu with the [ESC] key.
High sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer
taken into account for the level measurement. A false echo memory
should be created with low level so that all potential interfering reflec-
tions can be detected.
False signal suppression
Change now?
Proceed as follows:
1. Move from the measured value display to the main menu by
pushing [OK].
2. Select the menu item "Service" with [->] and confirm with [OK].
Now the menu item "False signal suppression" is displayed.
Linearization curve
Sensor-TAG
False signal suppression