6 Set up with the display and adjustment module PLICSCOM

VEGASON 63 • 4 … 20 mA/HART - two-wire

28777-EN-130417

3. Confirm "False signal suppression - Change now" with [OK] and

select in the below menu "Create new". Enter the actual distance

from the sensor to the product surface. All false signals in this

area are detected by the sensor and saved after confirming with

[OK].

Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.

The menu item "Extended setting" offers the possibility to optimise

VEGASON 63 for applications in which the level changes very quickly.

To do this, select the function "Quick level change > 1 m/min.".

Extended setting

quick level change > 1 m/min.

Note:

Since with the function "Quick level change > 1 m/min." the genera-

tion of an average value of the signal processing is considerably

reduced, false reflections by agitators or vessel installations can

cause measured value fluctuations. A false echo memory is thus

recommended.

This function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the display

and adjustment module. A description of the function is available in

the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:

Measured value presentation

Adjustment

Medium

Vessel form

Damping

Linearization curve

Sensor-TAG

Displayed value

Display unit

Scaling

Current output

Unit of measurement

Language

The following safety-relevant data are not read out or written:

HART mode

PIN

Copy sensor data

Copy sensor data?

Extended setting/Quick

level change

Copy sensor data