6 Set up with the display and adjustment module PLICSCOM
VEGASON 63 • 4 … 20 mA/HART - two-wire
28777-EN-130417
Basic adjustment
If the function "Reset" is carried out, the sensor resets the values of
the following menu items to the reset values (see chart):
2)
Function
Reset value
Sensor address
126
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in m(d)
3)
Medium
Liquid
Vessel form
not known
Damping
0 s
Linearization
Linear
Sensor-TAG
Sensor
Displayed value
Distance
Current output - characteristics
4 … 20 mA
Current output - max. current
20 mA
Current output - min. current
4 mA
Current output - failure
< 3.6 mA
Unit of measurement
m(d)
The values of the following menu items are not reset to the reset
values (see chart) with "Reset":
Function
Reset value
Backlight
No reset
Language
No reset
HART mode
No reset
Default setting
Like basic adjustment, but in addition, special parameters are reset to
default values.
4)
Peak value
The min. and max. distance and temperature values are reset to the
actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following
menu schematic. You will find a detailed description of these menu
items in the operating instructions manual "Display and adjustment
module".
Reset
Optional settings
2)
Sensor-specific basic adjustment.
3)
Depending on the sensor type, see chapter "Technical data".
4)
Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.