VEGA VEGADIF 55 Service instructions User Manual

Page 11

Advertising
background image

Code

Message
type/NA
64

Message/De-
scription

Cause

Measure

Priority

706 (W706) Warning C

C> Configura-
tions, data mem-
ory module and
instrument are
different

l

Configurations (pa-
rameter sets) in the
data memory module
and in the instrument
unequal

l

Copy data from device
into the data memory
module (see operating
instructions manual
VEGADIF 55, chapter
"C

opy configuration

data")

l

Copy data from device
into the memory mod-
ule (see also operating
instructions manual
VEGADIF 55, chapter
"C

opy configuration

data"). If the data
memory module and
the instrument have
different software ver-
sion, the message still
exists. The message
extinguishes when you
copy data from the
device into the data
memory module.

l

Instrument reset co-
des such as e.g. 7864
do not influence His-
toROM. I.e. if you
carry out a reset, the
configurations in His-
toROM and in the in-
strument can be un-
equal.

59

707 (W707) Alarm B

B> X-value of the
linearization
chart outside the
editing limits

l

At least one X-value of
the linearization chart
is either below the
value for HYDR.
PRESSURE MIN. or
MIN. LEVEL or above
the value for HYDR.
PRESSURE MAX. or
MAX. LEVEL.

l

Carry out a fresh ad-
justment (see operat-
ing instructions man-
ual VEGADIF 55)

38

710 (W710) Warning C

C> Set span is
smaller than per-
missible

l

Values for adjustment
(e.g. meas. start and
end) are too close
together

l

The sensor was ex-
changed and the cus-
tomer-specific param-
eter settings do not fit
the sensor

l

Unsuitable download
carried out

l

Adapt the adjustment
according to the sen-
sor (see operating in-
structions manual VE-
GADIF 55)

l

Replace the sensor
with another suitable
one

l

Check the parameter
adjustment and carry
out a fresh download

51

Service instructions VEGADIF 55