VEGA VEGADIF 55 Service instructions User Manual

Page 15

Advertising
background image

Code

Message
type/NA
64

Message/De-
scription

Cause

Measure

Priority

732 (A732)

Error C

C> Tmin.
PROCESS

underrun

l

Measured tempera-
ture value has fallen
short of the value
specified for parame-
ter Tmin. PROCESS

l

Check system/meas-
ured temperature val-
ue

l

If necessary, change
value for Tmin.
PROCESS (see oper-
ating instructions
manual VEGADIF 55,
parameter description
Tmin. PROCESS)

48

733 (A733)

Error C
factory set-
ting warn-
ing

C> Tmax.
PROCESS ex-
ceeded

l

Measured tempera-
ture value has ex-
ceeded the value
specified for parame-
ter Tmax. PROCESS

l

Check system/meas-
ured temperature val-
ue

l

If necessary, change
value for Tmax.
PROCESS (see oper-
ating instructions
manual VEGADIF 55,
parameter description
Tmax. PROCESS)

47

736 (A736)

Alarm B

B> RAM error

l

Fault in the main elec-
tronics

l

Main electronics de-
fective

l

Separate instrument
briefly from voltage
supply

l

Exchange the main
electronics

4

737 (A737)

Alarm B

B> Measure-
ment transmis-
sion error

l

Fault in the main elec-
tronics

l

Main electronics de-
fective

l

Separate instrument
briefly from voltage
supply

l

Exchange the main
electronics

20

738 (A738)

Alarm B

B> Measure-
ment transmis-
sion error

l

Fault in the main elec-
tronics

l

Main electronics de-
fective

l

Separate instrument
briefly from voltage
supply

l

Exchange the main
electronics

19

738 (A738)

Alarm B

B> Measure-
ment transmis-
sion error

l

Fault in the main elec-
tronics

l

Main electronics de-
fective

l

Separate instrument
briefly from voltage
supply

l

Exchange the main
electronics

23

Service instructions VEGADIF 55

15

Maintenance and fault rectification