VEGA VEGABAR 63 4 … 20 mA_HART User Manual

Page 40

Advertising
background image

P

roceed as follows:

1

E

dit the mbar value in the menu item "zero" with [OK].

Z

ero adjustment

000.0 %

P

=

+0000

.0 mbar

0000.0

mbar

2

S

et the requested mbar value with [+] and [->].

3

C

onfirm with [+] and move to span adjustment with [->].

T

he zero adjustment is finished.

Information:
T

he zero adjustment shifts the value of the span adjustment. The span,

i.e. the difference between these values, however, remains un-
changed.

Information:
F

or an adjustment with pressure, you simply enter the displayed actual

measured value. If the adjustment ranges are exceeded, the message
"O

utside parameter limits" appears. The editing procedure can be

aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

P

roceed as follows:

1

E

dit the mbar value in the menu item "span" with [OK].

S

pan adjustment

100.0 %

P

=

+1000

.0 mbar

0000.0

mbar

Information:
T

he displayed pressure for 100 % corresponds to the nominal

measuring range of the sensor (in the above example 1 bar =
1000

mbar).

2

S

et the requested mbar value with [->] and [OK].

3

C

onfirm with [OK] and move to the menu overview with [ESC].

T

he span adjustment is finished.

Information:
F

or an adjustment with pressure, you simply enter the displayed actual

measured value. If the adjustment ranges are exceeded, the message
"O

utside parameter limits" appears. The editing procedure can be

aborted with [ESC] or the displayed limit value can be accepted with
[OK]

.

Carrying out zero ad-
justment

Carrying out span ad-
justment

40

VEGABAR

63 • 4 … 20

mA/HART

6 S

et up with the indicating and adjustment module PLICSCOM

32462

-EN

-081209