VEGA VEGABAR 63 4 … 20 mA_HART User Manual

Page 57

Advertising
background image

A

djustment range of the zero/span adjustment relating to the nominal measuring range:

-

zero

-5 … +95 %

-

S

pan

-5 … +105 %

R

ecommended max. turn down

10 : 1 (

no limitation)

Nominal measuring ranges and overload resistance

Nominal range

Overload, max. pressure Overload, min. pressure

G

auge pressure

0 … 0.4

bar/0 … 40 kPa

2

bar/200 kPa

-1

bar/-100 kPa

0 … 1.6

bar/0 … 160 kPa

10

bar/1000 kPa

-1

bar/-100 kPa

0 … 16

bar/0 … 1.6 MPa

80

bar/8 MPa

-1

bar/-100 kPa

0 … 40

bar/0 … 4 MPa

80

bar/8 MPa

-1

bar/-100 kPa

0 … 100

bar/0 … 10 MPa

200

bar/20 MPa

-1

bar/-100 kPa

0 … 250

bar/0 … 25 MPa

500

bar/50 MPa

-1

bar/-100 kPa

0 … 600

bar/0 … 60 MPa

1200

bar/120 MPa

-1

bar/-100 kPa

-1 … 3

bar/-100 … 300 kPa

17

bar/1700 kPa

-1

bar/-100 kPa

-1 … 5

bar/-100 … 500 kPa

35

bar/3500 kPa

-1

bar/-100 kPa

-1 … 15

bar/-100 … 1.5 MPa

80

bar/8 MPa

-1

bar/-100 kPa

A

bsolute pressure

0 … 0.4

bar/0 … 40 kPa

2

bar/200 kPa

0

bar abs.

0 … 1.6

bar/0 … 160 kPa

10

bar/1000 kPa

0

bar abs.

0 … 6

bar/0 … 600 kPa

35

bar/3500 kPa

0

bar abs.

0 … 16

bar/0 … 1.6 MPa

80

bar/8 MPa

0

bar abs.

Reference conditions and actuating variables (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

18 … +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

D

etermination of characteristics

L

imit point adjustment according to IEC 61298-2

C

haracteristics

linear

R

eference installation position

upright, diaphragm points downward

I

nfluence of the installation position

depending on the isolating diaphragm version

Deviation determined according to the limit point method according to IEC 60770

11)

A

pplies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue

current output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) is the relation
nominal measuring range/set span.

11)

I

ncl. non-linearity, hysteresis and non-repeatability.

VEGABAR

63 • 4 … 20

mA/HART

57

10 S

upplement

32462

-

EN

-081209