5 Connecting to power supply

VEGAMET 381 Ex • 4 … 20 mA signal conditioning instrument

30418-01-131025

sensors and power supply units.

Select power supply

The power supply can be 20 … 253 V AC,

50/60 Hz or 20 … 253 V DC.
Select connection cable

The operating voltage of VEGAMET 381 Ex is

connected with standard cable according to the

national installation standards.
The instrument is connected with standard

two-wire cable without screen. If electromag-

netic interference is expected which is above

the test values of EN 61326 for industrial areas,

screened cable should be used.
Cable screening and grounding

Connect the cable screen on both ends to

ground potential. In the sensor, the screen must

be connected directly to the internal ground

terminal. The ground terminal outside on the

sensor housing must be connected to the

potential equalisation.
If potential equalisation currents are expected,

the screen connection on the side of VEGAMET

381 Ex must be made via a ceramic capacitor

(e. g. 1 nF, 1500 V). The low frequency potential

equalisation currents are thus suppressed, but

the protective effect against high frequency

interference signals remains.
Select connection cable for Ex applications

Take note of the corresponding instal-

lation regulations for Ex applications. In

particular, make sure that no potential

equalisation currents flow over the cable

screen. In case of grounding on both

sides this can be achieved by the use

of a capacitor or a separate potential

equalisation.

5.2 Input mode active/passive

On the rear of the instrument you can find a

cover which can be opened with a screwdriver.

Subjacent there is a slide switch by means of

which you can switch over between active and

passive mode of the measuring data input.

In active mode, VEGAMET 381 Ex provides

the power for the connected sensors. Power

supply and measurement data are transmit-

ted over the same two-wire cable. This mode

is provided for connection of measuring

transducers without separate operating

voltage (sensors in two-wire version).

In passive mode the sensors are not powe-

red, only the measured value is transmitted.

This input is for connection of transmitters

with their own separate operating voltage

(sensors in four-wire version). The VEGA-

MET 381 Ex can be also looped into the

existing circuit like a normal ammeter.

The position of the slide switch also

influences the preconditions for Ex

implementation. Take note of the type

approval certificate or the conformity

certificate ofVEGAMET 381 Ex.

5.3 Connection procedure

Proceed as follows:
1. Mount VEGAMET 381 Ex
2. Connect sensor cable to terminal 1 and 2,

and where applicable, connect the screen

3. Connect power supply (switched off) to

terminal 5 and 6

4. If necessary, connect fail safe and operating

relay as well as current output

The electrical connection is hence finished.

After connection, it is absolutely ne-

cessary to plug the blue Ex separating

chamber to terminals 1 and 2 (sensor

input). This ensures the required dis-

tance of at least 50 mm (1.97 in) to other

instruments.

1. Place the Ex separating chamber as shown

below on the terminals of the sensor input

2. Lead the sensor cable towards the front and

out of the Ex separating chamber

3. Push the Ex separating chamber towards

the front until you hear it snap in