4 wiring plan, 1 adjustment system, 2 setup steps – VEGA VEGAMET 381 Ex User Manual

Page 25

Advertising
background image

25

6 Setup with the integrated display and adjustment unit

VEGAMET 381 Ex • 4 … 20 mA signal conditioning instrument

30418-01-131025

5.4 Wiring plan

Overview

+ -

1 2

+ -

3 4

18 17 16 15 14 13 12 11 10 9 8 7 6 5

N- L1+

on

1

2

1

2

%

1

2

3

4

5

6

7

Abb. 15: Wiring plan with two-wire sensor
1 Measurement data input, optionally available with

sensor power supply

2 Current output

3 Fail safe relay

4 Relay 2

5 Relay 1

6 Voltage supply

Tipp:

For parameter adjustment of connec-

ted HART sensors, the sockets are

integrated in the terminals of the meas.

data input. A VEGACONNECT can be

directly plugged in without the need of

an additional HART resistor.

6 Setup with the integrated

display and adjustment

unit

6.1 Adjustment system

The integrated display and adjustment unit is

for measured value display, adjustment and

diagnosis ofVEGAMET 381 Ex. Indication and

adjustment is carried out in the front via a clear

LC-display and a function switch as well as two

keys.
To open the cover, insert a screwdriver in the

two slots on the top and turn it slightly.

012

34

567

89

AB

C

-

+

1

2

1

3

8

7

6

5

2

4

Abb. 16: Display and adjustment elements
1 Status indication operating relay 1 and 2

2 Status indication fail safe relay

3 Status indication operation

4 [+/-] adjustment keys

5 Insertable tag for identification of the measure-

ment loop

6 Function switch

7 Mode switch for sensor input (active/passive) on

the rear of the instrument

8 LC display

Key functions

[Function switch] for selection of:

– Adjustment

– Relay switching points

– Indication scaling

– Current output

– Integration time

– Offset correction

[+/-] key:

– Change value of the parameters

By pushing the [+/-] key, you change the indivi-

dual parameters of the selected function. In this

phase, the processed parameter is flashing. By

briefly pushing the two keys simultaneously, you

save your settings. "Save" is briefly displayed.

6.2 Setup steps

Setup

Setup comprises mainly the adjustment of the

measurement loop. A scaling of the measured

value for the LC display and the adaptation of

the relay switching points are further settings.

Additional setup steps would be, if necessary,

setting an integration time (damping) to steady

the measured value or modifying the current