6 Setup with the integrated display and adjustment unit

VEGAMET 381 Ex • 4 … 20 mA signal conditioning instrument

30418-01-131025

output characteristics.
To clearly denote the measuring unit, the

supplied labels can be inserted in the cover. In

case several VEGAMET 381 Ex are used, each

measurement loop should be clearly labelled.
Switch-on phase

After being switched on, VEGAMET 381 Ex

first of all carries out a short self-check. The

following steps are carried out:

Internal check of the electronics

Indication of the firmware version

The output signal jumps briefly to the set

fault value

Then the actual measured value is displayed

and the corresponding current is transmitted to

the current output.
Measured value indication

The measured value indication shows the digital

indication value and also an analogue bargraph.

Here, it is absolutely necessary that the function

switch is set to position [ 0] ("OPERATE").
Function switch

The following functions can be selected via the

rotary switch:

0: Measured value display and simulation

1: Relay 1 switching point ON

2: Relay 1 switching point OFF

3: Relay 2 switching point ON

2: Relay 2 switching point OFF

5: Decimal point position of the scaling

6: Scaling for 100 %

7: Scaling for 0 %

8: Switch over current output 0/4 … 20 mA

9: Damping of the measured value (integra-

tion time)

A: Offset correction

B: Min. adjustment in percent through

change of the level

C: Max. adjustment in percent through

change of the level

D: Min. adjustment in mA without changing

the level

E: Max. adjustment in mA without changing

the level

F: No function

Offset correction

When a pressure transmitter is used, an offset

correction should be carried out first. These

instruments are factory-set in a certain position.

If the pressure transmitter is now mounted in a

different position, its measuring range is shifted

slightly. The zero point is readjusted by carrying

out the offset correction in uncovered (unpres-

surised) condition. The complete measuring

range will be shifted by the deviating amount.
1. Make sure that the pressure transmitter

is completely unpressurised, uncovered

(unimmersed) and mounted in its final posi-

tion.

2. Set the function switch to position [A ]. The

display indicates now the actual sensor

current in mA. Save the current status by

pushing the [+/- ] keys simultaneously.

Adjustment in mA without changing the

level

For this adjustment procedure, two sensor

current values (4 … 20 mA) must be entered

corresponding to the levels 0 % and 100 %.
When using a pressure transmitter, an offset

correction should be carried out to reach maxi-

mum accuracy. Carry out this offset correction

before adjustment and with the sensor unco-

vered (unimmersed).

Now select the position [D] or [E] on the

function switch, enter the current values in

mA for min. or max. adjustment and save

your settings.

Adjustment in % by changing the level

During this adjustment procedure, the cur-

rent level is assigned to a certain percentage

value. For this reason, percentage values that

correspond to the actual filling levels must be

entered for the min. and max. adjustment. The

ideal calibration is at 0 % and 100 %. Because

it is not always possible to empty or fill a

vessel completely, any value can of course be

entered. The greater the difference between

the two adjustment points, the more precise the

measurement. It does not matter which value is

entered first.

Select position [B] or [C] on the function

switch, enter the percentage values for the

min. and max. adjustment and save your

settings.

Relay outputs

Two operating relays are integrated inVEGA-

MET 381 Ex for level detection. First of all,

determine at which switching points the relays