6 Setup with the integrated display and adjustment unit

VEGAMET 381 Ex • 4 … 20 mA signal conditioning instrument

30418-01-131025

Reset

With a reset, all values set by the user will be

lost and are reset to factory settings.

Interrupt the power supply of VEGAMET

381 Ex. Push the [+/-] keys simultaneously

and hold them while you switch on the

power supply. The display shows "RES" and

the default settings will be restored. These

are the following:

Relay switch on points: 10 %

Relay switch off points: 100 %

Decimal point: 888.8

Display min.: 0

Display max.: 100.0

Integration time: 0 s

Offset correction: 0

Current output: 4 … 20 mA

Min. adjustment: 0 % or 4 mA

Max. adjustment: 100 % or 20 mA

6.3 Application example

An upright cylindrical (linear) tank has a

volume of 2700 l

The max. filling volume is 2650 l, the min.

filling volume 50 l

The level sensor in the vessel is a pressure

transmitter (passive), outputting a standar-

dised 4 … 20 mA signal

For further processing, an additional

4 … 20 mA output signal is required

The full and empty adjustment was carried

out directly in the sensor. The following

values are outputted:

– Max. volume (display max.) 20 mA =

2650 l

– Min. volume (display min.) 4 mA = 50 l

Relay 1 should switch on an emptying pump

at a level of 90 % and switch off the pump at

a level of 10 %

General procedure

1. Select the following functions with the rotary

switch.

2. Push one of the two [+/-] adjustment keys,

the digital indication flashes (if the rotary

switch is set to "OPERATE", the [+/-] keys

are inoperable)

3. Adjust the requested value with the [+/-]

keys. If you hold the key pushed, the digital

indication changes the value more quickly.

4. Save your settings by pushing the [+/-] keys

simultaneously

Current output

1. Set the function switch to position [8]. Select

with the [+/-] keys the measured value

output 4 … 20 mA or 0 … 20 mA. For this

example, choose 4 - 20.

The displayed numbers have the following

meanings:

0 - 20 = 0 … 20 mA

4 - 20 = 4 … 20 mA

2. Save the value by pushing [+/-] simultane-

ously

VEGAMET 381 Ex requires for scaling of the

indication, the adjustment of the filling quantities

for 0 % and 100 %. The vessel must neither be

filled nor emptied.
Scaled indication at 0 %

1. Set the function switch to position [7] (dis-

play min.)

2. Set the value to 50 via the [+/-] keys
3. Save the value by pushing both keys simul-

taneously

Scaled indication at 100 %

1. Set the function switch to position [6] (dis-

play max.)

2. Set the value to 2650 via the [+/-] keys
3. Save the value by pushing both keys simul-

taneously

Decimal point

Since the range of the example tank is between

50 l and 2650 l, you need all 4 decimal places

for the digital indication.
1. Set the function switch to position [5] (Deci-

mal Point)

2. By pushing the [+/-] keys, you move the

decimal point

3. Save the value by pushing both keys simul-

taneously

Relay

Set the function switch to position [ 1 ]

(relay 1 on). For the given example, select

the value 90.0 (90.0 %) with the [ +/- ] keys.

The internal relay 1 then switches on when

this value is reached. Save the value by

pushing the two keys simultaneously.

Set the function switch to position [ 2]

(relay 1 off). Select the value 10.0 (10.0 %)

with the [ +/-] keys. The internal relay 1 then