VEGA VEGAMET 381 Ex User Manual

Page 32

Advertising
background image

32

9 Supplement

VEGAMET 381 Ex • 4 … 20 mA signal conditioning instrument

30418-01-131025

Switching current

min. 10 µA DC, max. 3 A AC, 1 A DC

Breaking capacity

min. 50 mW, max. 500 VA, max. 54 W DC

2)

Min. switching hysteresis

0.5 %

Current output
Quantity

1 x output

Range

0/4 … 20 mA

Resolution

0.1 %/20 µA

Max. load

500 Ω

Fault message

22 mA

Accuracy

±25 µA (0.125 % of 20 mA)

Temperature error (relating to 20 mA)

0.01 %/K

Indications
Measured value indication

Ʋ LC display (45 x 45 mm)

digital and quasianalogue indication

Ʋ Max. indicating range

-9999 … 9999

LED displays

Ʋ Status operating voltage

1 x LED green

Ʋ Status fault signal

1 x LED red

Ʋ Status operating relay 1/2

2 x LED yellow

Operation
Adjustment elements

2 x keys in the front, 1 x function switch, 1 x slide switch

active-passive

Ambient conditions
Ambient temperature

-20 … +60 °C (-4 … +140 °F)

Storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Electrical protective measures
Protection rating

Ʋ Wall, rail mounting

IP 20

Ʋ Front panel mounting

IP 40

Overvoltage category

II

Protection class

II

Electrical separating measures
Reliable separation according to VDE 0106 part 1 between power supply, sensor input and digital

component

Ʋ Reference voltage

250 V

Ʋ Voltage resistance of the isolation

3.75 kV

2)

If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be

permanently damaged. The contact is then no longer suitable for switching low-level signal circuits.

Advertising