VEGA VEGAFLEX 66 (-110…+400°C) Profibus PA User Manual

Page 29

Advertising
background image

Keep in mind that interfaces can cause faulty measurements.

If you want to measure the total height of both liquids reliably,
please contact our service department or use an instrument
specially designed for interface measurement.

Start your parameter adjustment with the following menu items
of the basic adjustment:

Proceed as follows:

1 Move from the measured value display to the main menu

by pushing [OK].

Basic adjustment

Display
Diagnostics
Service
Info

2 Select the menu item "Basic adjustment" with [->] and

confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.

Min. adjustment

0.00 %

=

10.000 m(d)

8.000 m(d)

3 Prepare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.

4 Enter the suitable distance value in m for the empty vessel

(e.g. distance from the sensor to the vessel bottom)
corresponding to the percentage value.

5 Save the settings with [OK] and move to "Max. adjustment"

with [->].

Proceed as follows:

Max. adjustment

100.00 %

=

1.000 m(d)

2.000 m(d)

1 Prepare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.

Carrying out min. ad-
justment

Carrying out max. ad-
justment

VEGAFLEX

66 • Profibus PA

29

6 Set up with the indicating and adjustment module PLICSCOM