Adjustment error, Unit irregularity, Error in the linearization table – VEGA VEGAFLEX 66 (-110…+400°C) Profibus PA User Manual

Page 58: Hardware error, Converter error, Leakage pulse error, Trigger error, Measured value generation error, Switch on simulation

Advertising
background image

Byte n

Byte n+1

Bit

7

VZ

Exponent

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Sign

Bit

Significant

7

6

5

4

3

2

1

0

-1

-2

-3

-4

-5

-6

-7

Byte n+2

Byte n+3

Bit

7
2

Significant

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Significant

-9

-10 -11 -12 -13 -14 -15 -16 -17

-18 -19

-20 -21 -22 -23

-8

Value = (-1)

VZ

2

(Exponent - 127)

(1 + Significant)

Fig. 29: Data format of the measured value

Coding of the status byte associated with the PA output value

Status
code

Description according to Pro-
fibus standard

Possible cause

0x00

bad - non-specific

Flash-Update active

0x04

bad - configuration error

l

Adjustment error

l

Configuration error with PV-Scale (PV-Span too
small)

l

Unit irregularity

l

Error in the linearization table

0x0C

bad - sensor failure

l

Hardware error

l

Converter error

l

Leakage pulse error

l

Trigger error

0x10

bad - sensor failure

l

Measured value generation error

0x1f

bad - out of service constant

"O

ut of Service" mode switched on

0x44

uncertain - last unstable value

Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)

0x48

uncertain substitute set

l

Switch on simulation

l

Failsafe replacement value (Failsafe-Mode =
"F

safe value")

0x4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)

0x51

uncertain - sensor; conversion
not accurate - low limited

Sensor value < lower limit

0x52

uncertain - sensor; conversion
not accurate - high limited

Sensor value > upper limit

0x80

good (non-cascade) - OK

OK

0x84

good (non-cascade) - active
block alarm

Static revision (FB, TB) changed (10 sec. active, after the parameter
of the static category was written)

0x89

good (non-cascade) - active ad-
visory alarm - low limited

Lo-Alarm

58

VEGAFLEX

66 • Profibus PA

10 Supplement

32764

-EN

-080716