VEGA VEGAFLEX 66 (-110…+400°C) Profibus PA User Manual

Page 57

Advertising
background image

l

Long for Profibus master only supporting the "Identifier
Format" byte, e.g. Siemens S7-300/400

Examples of telegram configuration
In the following you will see how the modules can be combined and how the appendant
data telegram is structured.

Example 1 (standard setting) with distance value and additional cyclical value:

l

AI (PA-OUT)

l

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

Status

Status

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

IEEE-754-

Floating point value

Additional Cyclic

Value

Format

Value

Example 2 with distance value without additional cyclical value:

l

AI (PA-OUT)

l

Free Place

Byte-No.

1

2

3

4

5

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

Format

Value

Data format of the output signal

Byte4

Byte3

Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 28: Data format of the output signal

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control
Devices" coded. The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0
=

0).

The measured value is transferred as a 32 bit floating point number in the IEEE-754
format.

VEGAFLEX

66 • Profibus PA

57

10 Supplement

32764

-

EN

-080716