6 Set up with the display and adjustment module

MINITRAC 31 • 4 … 20 mA/HART - four-wire

40447-EN-131119

Additional adjustments

The following reset functions are available:

Basic settings: Resetting of the parameter adjustments to default

values at the time of shipment. Order-specific settings are deleted.
Default settings: Resetting of the parameter adjustment like under

"Basic settings". In addition, special parameters are reset to default

values. Order-specific settings are deleted.
Peak values of measured value: Resetting of the parameter adjust-

ments in the menu item "Setup" to the default values of the respective

instrument. Order-specific settings remain but are not taken over into

the current parameters.
Peak values of temperature: Resetting of the measured min. and

max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The

values apply for the application "Level". First of all you have to select

the application.
Depending on the instrument version, not all menu items may be

available or they may be differently assigned:

Menu

Menu item

Default value

Setup

Measurement loop name

Sensor

Isotope

Cs-137

Application

Level

Background radiation

0 ct/s

Unit of the process value

m

Temperature unit

° C

Damping

60 s

Real value correction

0

Current output mode

4 … 20 mA, < 3.6 mA

Current output Min./Max.

Min. current 3.8 mA, max. current 20.5 mA

X-ray alarm

Modulated measuring current

Reference value - Relay

None

Block adjustment

Released

Display

Language

Selected language

Displayed value

Pulse rate

Display unit

ct/s

Additional adjustments

Temperature unit

°C

Linearisation curve

Empty

HART mode

Standard
Address 0

Additional adjustments

- Reset