8 saving the parameter adjustment data – VEGA MINITRAC 31 4 … 20 mA_HART - four-wire User Manual

Page 60

Advertising
background image

60

6 Set up with the display and adjustment module

MINITRAC 31 • 4 … 20 mA/HART - four-wire

40447-EN-131119

The MINITRAC 31 requires this information for the decay compensa-

tion. An annual recalibration is hence not necessary.
Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-

plication. You can choose between the following applications: "Level",

"Density", "Limit level", "X-ray alarm" or "Real value correction".

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual

"Display and adjustment module".

6.8 Saving the parameter adjustment data

We recommended noting the adjusted data, e.g. in this operating

instructions manual, and archiving them afterwards. They are thus

available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,

the data in the sensor can be saved in the display and adjustment

module. The procedure is described in the operating instructions

manual "Display and adjustment module" in the menu item "Copy

sensor data". The data remain there permanently even if the sensor

power supply fails.
The following data or settings for adjustment of the display and ad-

justment module are saved:

All data of the menu "Setup" and "Display"

In the menu "Additional adjustments" the items "Sensor-specific

units, temperature unit and linearization"

The values of the user programmable linearization curve

The function can also be used to transfer settings from one instru-

ment to another instrument of the same type. If it is necessary to

exchange a sensor, the display and adjustment module is inserted

into the replacement instrument and the data are likewise written into

the sensor via the menu item "Copy sensor data".

Setup/Application

Lock setup - adjustment

Advertising