6 Set up with the display and adjustment module

MINITRAC 31 • 4 … 20 mA/HART - four-wire

40447-EN-131119

Linearization - Modify

You can also modify individual linearization points.

After editing, you have to activate the complete value pair so that the

linearization point will be effective.

You recognize active linearization points by a small square with a

cross next to the number of the linearization point.

In this menu item you can adjust the damping of the sensor. With

it you can suppress fluctuations in the measured value indication,

caused e.g. by an agitated product surface. This time can be between

1 and 1200 seconds. Keep in mind that the reaction time also in-

creases and the instrument reacts to quick level changes with a delay.

Generally a time of approximately 60 seconds is sufficient to smooth

the measured value indication.
With the setting "Automatic", the instrument itself calculates a suitable

damping on the basis of the adjustment and the measured value

changes. This setting is particularly suitable for application where fast

and slow level changes occur.

The implementation of a real value corretion is only necessary if the

requirements of the measurement loop have changed, for example

with abrasion in a tube.
If you know the density of a certain medium, you can enter the deter-

mined real density in this menu item to correct the measured value.

The function shifts the linearization curve to this determined point.
The measurement can thus be adapted exactly to the conditions in

the tube.

Setup/Damping

Setup/Real value correc-

tion (manually)