VEGA MINITRAC 31 4 … 20 mA_HART - four-wire User Manual

Page 46

Advertising
background image

46

6 Set up with the display and adjustment module

MINITRAC 31 • 4 … 20 mA/HART - four-wire

40447-EN-131119

Menu

Menu item

Default value

Setup

Measurement loop name

Sensor

Isotope

Cs-137

Application

Density

Background radiation

0 ct/s

Unit of the process value

g/cm

3

Temperature unit

° C

Adjustment min. process

value

0.500 g/cm

3

Adjustment max. process

value

1.500 g/cm

3

Inner diameter

0.20 m

Linearization

90000 ct/s and 0.500 g/cm

3

Damping

60 s

Real value correction

0

Current output mode

4 … 20 mA, < 3.6 mA

Current output Min./Max.

Min. current 3.8 mA, max. current 20.5 mA

X-ray alarm

Modulated measuring current

Reference value - Relay

None

Block adjustment

Released

Display

Language

Selected language

Displayed value

Pulse rate

Display unit

ct/s

Additional adjustments

HART mode

Standard
Address 0

With this function you can select the mode.

The sensor offers the HART modes standard and multidrop.
The mode 'Standard' with the fixed address 0 (factory setting) means

output of the measured value as 4 … 20 mA signal.
This parameter is described in the operating instructions manual

"Display and adjustment module".

With this function

Load parameter adjustment data from the sensor into the display

and adjustment module

Write parameter adjustment data from the display and adjustment

module into the sensor

This parameter is described in the operating instructions manual

"Display and adjustment module".
Info

In this menu you will find the following menu items:

Additional adjustments/

HART mode

Additional adjustments -

Copy instrument settings

Info