VEGA WEIGHTRAC 31 4 … 20 mA_HART - four-wire User Manual

Page 35

Advertising
background image

35

6 Adjustment with the display and adjustment module

WEIGHTRAC 31 • 4 … 20 mA/HART - four-wire

42374-EN-131119

for correct operation. Push the button "OK" to acknowledge the error

message. Carry out the adjustment with PACTware.
With the display and adjustment module you can only read out the pa-

rameters of the WEIGHTRAC 31. Carry out the parameter adjustment

of the instrument with the adjustment software PACTware.
You can find the parameter adjustment in the next chapter.
Setup
In this menu item you can read out the set application.

Display

With this parameter you can change the display language.

This parameter is described in the operating instructions manual

"Display and adjustment module".

With this parameter you can change the indication of the display.

You can choose if the display should show the actual pulse rate, the

output current, the electronics temperature or the percentage value.

Diagnostics
In this menu item, you can enquire the status of your sensor. In normal

operation, the sensor displays the message "OK". In case of fault, you

will find the corresponding fault code here.
This parameter is described in the operating instructions manual

"Display and adjustment module".

The peak value function holds the max. and min. values during opera-

tion.
This parameter is described in the operating instructions manual

"Display and adjustment module".

Here you can retrieve the adjustment value of the sensor. This is the

percentage value of the difference of the min. and max. adjustment

points (Delta I). The value is an indication for the reliability and repro-

ducibility of the measurement.
The higher the difference between the two adjustment points,

the higher the differential value (Delta I) and the more reliable the

measurement. A Delta I value below 10 % is an indication for a critical

measurement.

Setup/Application

Display - Language

Display/Displayed value

Diagnostics - Device

status

Diagnosis - Peak value

Diagnosis - Adjustment

data

Advertising