8 Diagnosis, asset management and service

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

8.5 Calculation of total deviation (according to

DIN 16086)

The total deviation of a pressure transmitter indicates the maximum

measurement error to be expected in practice. It is also called maxi-

mum practical deviation or operational error.
According to DIN 16086, the total deviation F

total

is the sum of the

basic accuracy F

perf

and the long-term stability F

stab

:

F

total

= F

perf

+ F

stab

The basic accuracy F

perf

is composed of the deviation F

Kl

and the

thermal change of zero signal and output span F

T

:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

To provide a better overview, the formula symbols are listed together

below:

F

total

: Total deviation

F

perf

: Basic accuracy

F

stab

: Long-term drift

F

T

: Thermal change of zero signal and output span

F

Kl

: Deviation

You can find the specifications in chapter "Technical data".

Level measurement 1500 mmWs
Product temperature up to 40 °C
VEGABAR 87 with measuring range 0.2 bar
Deviation < 0.1 %
Calculation ΔT: ΔT = 40 °C - 20 °C = 20 K
Calculation of the set Turn Down:
TD = 200 mbar/147 mbar, TD = 1.4
1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.1 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.1 %)

2

)

F

perf

= 0.21 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.4)

F

stab

= 0.07 %

F

total

= 0.21 % + 0.07 % = 0.28 %

Meaning of the total

deviation

Practical example

Calculation