5 levelmaster commands – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 68

Advertising
background image

68

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Confirmity Level

1 Byte

0x01, 0x02, 0x03, 0x81, 0x82, 0x83

More follows

1 Byte

00/FF

Next Object ID

1 Byte

Object ID number

Number of Objects

1 Byte

List of Object ID

1 Byte

List of Object length

1 Byte

List of Object value

1 Byte

Depending on the Object ID

10.5 Levelmaster commands

The VEGABAR 87 is also suitable for connection to the following RTUs with Levelmaster protocol.

The Levelmaster protocol is often called "Siemens" "Tank protocol".

RTU

Protocol

ABB Totalflow

Levelmaster

Kimray DACC 2000/3000

Levelmaster

Thermo Electron Autopilot

Levelmaster

Parameters for the bus communication

The VEGABAR 87 is preset with the default values:

Parameter

Configurable Values

Default Value

Baud Rate

1200, 2400, 4800, 9600, 19200

9600

Start Bits

1

1

Data Bits

7, 8

8

Parity

None, Odd, Even

None

Stop Bits

1, 2

1

Address range Levelmaster

32

32

The Levelmaster commands are based on the following syntax:

Capital letters are at the beginning of certain data fields

Small letters stand for data fields

All commands are terminated with "<cr>" (carriage return)

All commands start with "Uuu", whereby "uu" stands for the address (00-31)

"*" can be used as a joker for any position in the address. The sensor always converts this in

its address. In case of more than one sensor, the joker must not be used, because otherwise

several slaves will answer

Commands that modify the instrument return the command with "OK“. "EE-ERROR" replaces

"OK" if there was a problem changing the configuration