75

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Bristol ControlWave Micro

Wiring plan

+

+

power supply

MODBU

S

D0

D1

IS GND

US

B

1

2

3

13

45

2o

ff

on

(

)

(

)

(-)

(-)

+8

+30 Vdc

to

GND

1 +SV

RS

485 on COM1

2 RX-

5 RXT

6 TXT

3 TX-

4 GND

7 not used

8 not used

Fig. 33: Connection of VEGABAR 87 to RTU Bristol ControlWave Micro
1 VEGABAR 87

2 RTU Bristol ControlWave Micro

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

2 (FC4)

RTU Data Type

32-bit registers as 2 16-bit registers

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGABAR

87.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave

Micro.