Report level (and temperature), Report unit number, Assign unit number – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 69

Advertising
background image

69

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Report Level (and Temperature)

Request:

Parameter

Length

Code/Data

Report Level (and Temperature)

4 characters ASCII

Uuu?

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

24 characters ASCII

UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1

level data not readable)
wwww = Warning number (0 no

warning)

Level in inches is repeated for sensors with 2 levels. PV value is transmitted as first measured value,

SV as second measured value.
PV, SV, TV and QV can be adjusted via the sensor DTM.

Report Unit Number

Request:

Parameter

Length

Code/Data

Report Unit Number

5 characters ASCII

U**N?

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

6 characters ASCII

UuuNnn

Assign Unit Number

Request:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address

Advertising