4 modbus rtu commands, Fc3 read holding register, Fc4 read input register – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 65

Advertising
background image

65

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Unit Code

Measurement Unit

47

Inches

48

Centimeters

49

Millimeters

111

Cubic Yards

112

Cubic Feet

113

Cubic Inches

10.4 Modbus RTU commands

FC3 Read Holding Register

With this command, any number (1-127) of holding registers can be read out. The start register,

from which the readout should start, and the number of registers are transmitted.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x03

Start Address

2 Bytes

0x0000 to 0xFFFF

Number of Registers

2 Bytes

1 to 127 (0x7D)

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x03

Start Address

2 Bytes

2*N

Register Value

N*2 Bytes

Data

FC4 Read Input Register

With this command, any number (1-127) of input registers can be read out. The start register, from

which the readout should start, and the number of registers are transmitted.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x04

Start Address

2 Bytes

0x0000 to 0xFFFF

Number of Registers

N*2 Bytes

1 to 127 (0x7D)

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x04

Start Address

2 Bytes

2*N

Register Value

N*2 Bytes

Data

Advertising