VEGA VEGAFLEX 82 Modbus and Levelmaster protocol User Manual
Page 17
17
4 Mounting
VEGAFLEX 82 • Modbus and Levelmaster protocol
41833-EN-130314
Concrete vessel
When installed in thick concrete ceilings, VEGAFLEX 82 should be
mounted front flush to the lower edge. In concrete silos, the distance
to the wall should be at least 500 mm (20 in).
ø >160 mm
(ø >6.3")
Fig. 8: Installation in concrete silo
If possible, avoid sockets. Mount the sensor flush with the vessel top.
If this is not possible, use short sockets with small diameter.
Higher sockets or sockets with a bigger diameter can generally be
used. They simply increase the upper blocking distance. Check if this
is relevant for your measurement.
In such cases, always carry out a false signal suppression after instal-
lation. You can find further information under "Setup procedure".
h
d
d
h
DN40 ... DN150
> DN150 ... DN200
150
100
_<
_<
Fig. 9: Mounting socket
Socket