4 Mounting

VEGAFLEX 82 • Modbus and Levelmaster protocol

41833-EN-130314

Concrete vessel

When installed in thick concrete ceilings, VEGAFLEX 82 should be

mounted front flush to the lower edge. In concrete silos, the distance

to the wall should be at least 500 mm (20 in).

ø >160 mm

(ø >6.3")

Fig. 8: Installation in concrete silo

If possible, avoid sockets. Mount the sensor flush with the vessel top.

If this is not possible, use short sockets with small diameter.
Higher sockets or sockets with a bigger diameter can generally be

used. They simply increase the upper blocking distance. Check if this

is relevant for your measurement.
In such cases, always carry out a false signal suppression after instal-

lation. You can find further information under "Setup procedure".

h

d

d

h

DN40 ... DN150

> DN150 ... DN200

150
100

_<
_<

Fig. 9: Mounting socket