6 Set up with the display and adjustment module

VEGAFLEX 82 • Modbus and Levelmaster protocol

41833-EN-130314

In this menu item you can select the application. You can choose

between metallic oder non-metallic vessels.
Note:

The selection of the application has a considerable influence on all

other menu items. Keep in mind that as you continue with the param-

eter adjustment, individual menu items are only optionally available.
You have the possibility to choose the demonstration mode.This

mode is suitable for test and demonstration purposes. In this mode,

the sensor ignores the logic parameters of the application and reacts

immediately to each change.

In this menu item, you can define the medium type (product).
This menu item is only available if you have selected level measure-

ment under the menu item "Application".

You can choose between the following medium types:

Dielectric con-

stant

Medium type

Examples

> 3

Cereals, flour

All kind of cereals, wheat flour

1.5 … 3

Granules, cement Lime, gypsum, cement

< 1.5

Dusts, wood chips Wood chips, sawdust

In this menu item, you can enter the max. adjustment for the level.

Adjust the requested percentage value with [+] and save with [OK].

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor