11 Supplement

VEGAFLEX 82 • Modbus and Levelmaster protocol

41833-EN-130314

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Reflector

metallic, ø 1 m

Ʋ Medium

Bulk solids - cereals, flour, cement (dielectric con-

stant ~2.0)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

Gating out of false signals carried out

Typical deviation

2)

See following diagrams

L

0

-2 mm

(-0.079")

2 mm

(0.079")

15 mm

(0.591")

-10 mm

(-0.394")

0,3 m

(11.811")

0,08 m

(3.15")

0,02 m

(0.787")

1

Fig. 40: Deviation VEGAFLEX 82 in rod version
1 Dead band - no measurement possible in this area

L Probe length

2)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode