VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire, approval according to LPR radio standard User Manual
Page 19
When using a surge pipe in a vessel, influences from vessel
installations and turbulences can be excluded. Under these prereq-
uisites, the measurement of products with low dielectric values (ε
r
value ≥ 1.6) is possible. In very adhesive products, measurement in a
surge pipe is not recommended.
0%
100%
1
2
3
1
2
3
4
5
8
6
7
9
Fig. 13: Configuration surge pipe
1
Radar sensor
2
Marking of the polarisation plane
3
Thread or flange on the instrument
4
Vent hole
5
Holes
6
Weld joint
7
Welding neck flange
8
Ball valve with complete opening
9
Fastening of the surge pipe
Instructions for orientation:
l
Note marking of the polarisation plane on the sensor
l
With threaded fitting, the marking is on the hexagon, with flange
connection between the two flange holes
l
The marking must show to the direction of the holes in the surge
pipe
Instructions for the measurement:
Measurement in a surge
pipe
VEGAPULS
62 • 4 … 20 mA/HART - two-wire, approval according to LPR radio standard
19
4 Mounting
41718
-EN
-120301