Measurement error during emptying – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire, approval according to LPR radio standard User Manual

Page 62

Advertising
background image

Fault description

Error pattern

Cause

Rectification

8. Measured value
jumps towards 100 %
during filling

Level

time

0

l Due to strong turbulence and

foam generation during filling,
the amplitude of the product
echo sinks. Measured value
jumps to the false echo

l Carry out false signal suppres-

sion

9. Measured value
jumps sporadically to
100 % during filling

Level

time

0

l Varying condensation or con-

tamination on the antenna

l Carry out a false signal sup-

pression or increase false sig-
nal suppression with
condensation/contamination in
the close range by editing

10. Measured value
jumps to ≥ 100 % or 0 m
distance

Le

ve

l

time

0

l Level echo is no longer de-

tected in the close range due
to foam generation or false
echoes in the close range. The
sensor goes into overfill pro-
tection mode. The max. level
(0 m distance) as well as the
status message "Overfill pro-
tection" are outputted.

l Check measuring site: Antenna

must protrude out of the socket

l Remove pollution on the an-

tenna

l Use a sensor with a more

suitable antenna

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

11. Measured value
remains unchanged in
the close range during
emptying

Level

time

0

l False echo larger than the

level echo

l Level echo too small

l Remove false echoes in the

close range. Check: Antenna
must protrude out of the socket

l Remove pollution on the an-

tenna

l Minimize interfering installa-

tions in the close range by
changing the polarization di-
rection

l After removing the false

echoes, the false signal sup-
pression must be deleted.
Carry out a new false signal
suppression

12. Measured value
jumps towards 0 % du-
ring emptying

Level

time

0

l The tank floor echo is larger

than the product echo, e.g.
with products with ε

r

<

2.5 oil-

based, solvents

l Application parameter "Me-

dium type", check Vessel
height and Floor form, adapt if
necessary

13. Measured value
jumps sporadically to-
wards 100 % during
emptying

Level

time

0

l Varying condensation or con-

tamination on the antenna

l Carry out false signal suppres-

sion or increase false signal
suppression in the close range
by editing

l With bulk solids use radar

sensor with purging air con-
nection

62

VEGAPULS

62 • 4 … 20 mA/HART - two-wire, approval according to LPR radio standard

9 Diagnosis, Asset Management and service