VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire, approval according to LPR radio standard User Manual

Page 56

Advertising
background image

Maintenance: Due to external influences, the instrument function is
limited. The measurement is affected, but the measured value is still
valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).

This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.

The following table shows the error codes in the status message
"F

ailure" and gives information on the reason and rectification. Keep in

mind that some information is only valid with four-wire instruments.

Code
Text mes-
sage

Cause

Rectification

F

013

no measured
value availab-
le

l Sensor does not detect an

echo during operation

l Antenna system contami-

nated or defective

l Check or correct installa-

tion and/or parameter ad-
justment

l Clean or exchange process

component or antenna

F

017

Adjustment
span too small

l Adjustment not within spe-

cification

l Change adjustment accor-

ding to the limit values
(difference between min.
and max. ≥ 10 mm)

F

025

Error in the li-
nearization
table

l Index markers are not

continuously rising, for
examle unlogical value
pairs

l Check linearization table
l Delete table/Create new

F

036

No operable
software

l Failed or interrupted soft-

ware update

l Repeat software update
l Check electronics version
l Exchange of the electro-

nics

l Send instrument for repair

F

040

Error in the
electronics

l Hardware defect

l Exchange of the electro-

nics

l Send instrument for repair

F

080

l General software error

l Separate operating voltage

briefly

F

105

Determine
measured va-
lue

l The instrument is still in the

start phase, the measured
value could not yet be
determined

l Wait for the warm-up phase
l Duration depending on the

version and parameter ad-
justment up to approxima-
tely 3 min.

F

113

Communicati-
on error

l EMC interferences
l Transmission error with the

external communication
with 4-wire power supply
unit

l Remove EMC influences
l Exchange 4-wire power

supply unit or electronics

Failure

56

VEGAPULS

62 • 4 … 20 mA/HART - two-wire, approval according to LPR radio standard

9 Diagnosis, Asset Management and service

41718

-EN

-120301

Advertising