6 Set up with the display and adjustment module
VEGAFLEX 82 • Profibus PA
44220-EN-130910
In this menu item, you can define the type of medium (product).
This menu item is only available if you have selected level measure-
ment under the menu item "Application".
You can choose between the following medium types:
Dielectric con-
stant
Product type
Examples
> 3
Cereals, flour
All kind of cereals, wheat flour
1.5 … 3
Granules, cement Lime, gypsum, cement
< 1.5
Dusts, wood chips Wood chips, sawdust
In this menu item, you can enter the max. adjustment for the level.
Adjust the requested percentage value with [+] and store with [OK].
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
reference plane (seal surface of the process fitting). Keep in mind that
the max. level must lie below the dead band.
In this menu item, you can enter the min. adjustment for the level.
Adjust the requested percentage value with [+] and store with [OK].
Setup - Medium, dielec-
tric constant
Setup - Max. adjustment
Level
Setup - Min. adjustment
Level