7 Setup with PACTware

VEGAFLEX 82 • Profibus PA

44220-EN-130910

Serial number

Here, you can find the serial number of your instrument. You cannot

change this line because the serial number is unmodifiably saved in

the instrument.
Measurement loop name

Here you can enter a suitable measurement loop name for your VE-

GAFLEX 82. You can enter a name with max. 19 characters. You can

use capital and small letters as well as numbers. The following special

characters are also possible: + - . : , ( ) / < >
Probe length modified?

If you have modified the probe length, this must be entered in the

selection field.

If you select "No", then the instrument uses automatically the

preset length of the default setting.

If you select "Yes", then you can enter in another field the modified

length of the instrument.

Instrument address

An address must be assigned to each Profibus PA instrument. Each

address may only be assigned once in the Profibus PA network. The

sensor is only recognized by the control system if the address is set

correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

Hardware addressing - The hardware addressing is effective if an

address <126 is set with the address selection switches on the

electronics module of VEGAFLEX 82. The software addressing is

then no longer effective, only the set hardware address is valid.

Software addressing - The software addressing is only effective

if address 126 or higher is set on the instrument with the address

selection switches.

Probe length L from seal surface

If you have modified the length of the probe, you can enter in this field

the modified probe length. Keep the selected unit in mind.
Determine probe length automatically

If you do not know the probe length, you can have the length of the

probe determined automatically. The requirement for this is a probe

unrestricted and not covered by the medium.
Click to "Carry out now", to start the automatic length determination.