80

11 Supplement

VEGAFLEX 82 • Profibus PA

44220-EN-130910

Ʋ 1. FB

PV

Ʋ 2. FB

SV 1

Ʋ 3. FB

SV 2

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

Ʋ Ex-d instruments

16 mA, ±0.5 mA

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Reflector

metallic, ø 1 m

Ʋ Medium

Bulk solids - cereals, flour, cement (dielectric con-

stant ~2.0)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation

2)

See following diagrams

L

0

-2 mm

(-0.079

")

2 mm

(0.079

")

15 mm

(0.591

"

)

-10 mm

(-0.394

")

0,3 m

(11.811

"

)

0,08 m

(3.15

"

)

0,02 m

(0.787

")

1

Fig. 58: Deviation VEGAFLEX 82 in rod version
1 Dead band - no measurement possible in this area

L Probe length

2)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode