9 Diagnostics and service

VEGAFLEX 82 • Profibus PA

44220-EN-130910

7. Cable: Fasten the cable with three pins, torque 20 Nm

(14.75 lbf in)
Cable ø 4: 7 Nm (5.16 lbf ft)
Cable ø 6, cable ø 8: 20 Nm (14.75 lbf ft)

8. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying

out max. adjustment").

3

1

2

2

A

B

45 mm (1.77"

)

150 mm (5.91"

)

70 mm (2.76"

)

150 mm (5.91"

)

Fig. 52: Shortening the cable probe
A Gravity weight - cable ø 4 mm

B Gravity weight - cable ø 6 mm

1 Pins

2 Thread M12 for eye-bolt

3 Pins

9.7 Software update

The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

Interface adapter VEGACONNECT

PC with PACTware

Current sensor software as file

You can find the actual sensor software as well as detailed infor-

mation of the procedure under "www.vega.com/downloads" and

"Software".
You can find information about the installation in the download file.
Caution:

Instruments with approvals can be bound to certain software ver-

sions. Therefore make sure that the approval remains effective with a

software update.