VEGA VEGAFLEX 82 Profibus PA User Manual

Page 46

Advertising
background image

46

6 Set up with the display and adjustment module

VEGAFLEX 82 • Profibus PA

44220-EN-130910

Menu item

Default value

Modified value

Accept adjustment of the level measurement?

Yes

Max. adjustment - Interface

100 %

Max. adjustment - Interface

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Interface

0 %

Min. adjustment - Interface

Distance: Probe length - take dead

band into account

Integration time - Level

0.0 s

Integration time - Interface

0.0 s

Linearization type

Linear

Linearization - Socket correction

0 mm

Linearization - Vessel height

Probe length

AI FB1 Tag Descriptor
AI FB1 Channel

Primary Value (lin. percent level)

AI FB1 scaling PV Scale (min.)

0 %

AI FB1 scaling PV Scale (max.)

100 %

AI FB1 Lin. Type

Linear

AI FB1 Out Scale Unit

%

AI FB1 Out Scale Decimal Point

#.##

AI FB1 Out Scale (min.)

0 %

AI FB1 Out Scale (max.)

100 %

AI FB1 PV FTime

0 s

AI FB1 Hi Hi Limit

3.402823E+38 %

AI FB1 Hi Limit

3.402823E+38 %

AI FB1 Lo Lo Limit

-3.402823E+38 %

AI FB1 Lo Limit

-3.402823E+38 %

AI FB1 Hysteresis

0.50 %

AI FB1 Fail Safe Mode (behaviour in case of mal-

function)

Last Valid Out Value (last valid

measured value)

AI FB1 Fail Safe Value

0.00 %

AI FB1 Target Mode

Auto

Display

Menu item

Default value

Modified value

Language

Order-specific

Displayed value 1

Filling height Level

Displayed value 2

Electronics temperature

Backlight

Switched off