5 connecting to power supply – VEGA VEGASWING 51 - contactless electronic switch User Manual

Page 12

Advertising
background image

12

5 Connecting to power supply

VEGASWING 51 • - contactless electronic switch

41045-EN-130322

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

The instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326 for industrial areas, screened cable should

be used.
Use cable with round cross section. Depending on the plug connec-

tion, you have to select the outer diameter of the cable respectively so

that the seal effect of the cable gland is ensured.

Valve plug ISO 4400, ø 4.5 … 7 mm

Valve plug ISO 4400 with IDC crimping technology, ø 5.5 … 8 mm

Use cable with a round wire cross section and tighten the cable gland.
When mounting outdoors, on cooled vessels or in moist areas in

which cleaning is made with steam or high pressure, the sealing of

the cable gland is very important.

5.2 Wiring plan

1

2

Fig. 6: Overview of the connection versions
1 Valve plug ISO 4400

2 Valve plug ISO 4400 with IDC method of termination

Note safety instructions

Connection cable

Cable glands

Housing overview

Advertising