4 Mounting

VEGASWING 51 • - contactless electronic switch

41045-EN-130322

4 Mounting

4.1 General instructions

Make sure that all parts of the instrument coming in direct contact

with the process, especially the sensor element, process seal and

process fitting, are suitable for the existing process conditions, such

as process pressure, process temperature as well as the chemical

properties of the medium.
You can find the specifications in chapter "Technical data" and on the

nameplate.

Generally, VEGASWING 51 can be mounted in any position. Just

install the instrument so that the tuning fork is at the height of the

requested switching point. Keep in mind that the switching point can

vary depending on the installation position.
The switching point refers to the medium water (1 g/cm³/0.036 lbs/

in³). Please keep in mind that the switching point of the instrument

shifts when the medium has a density differing from water.

2

3

1

11 mm (0.43")

34 mm (1.34")

Fig. 2: Mounting vertical
1 Switching point

2 Switching point with lower density

3 Switching point with higher density

2

1

Fig. 3: Mounting horizontal
1 Switching point

2 Switching point (recommended mounting position, particularly for adhesive

products)

Suitability for the process

conditions