5 Connecting to power supply

VEGASWING 51 • - contactless electronic switch

41045-EN-130322

1

2

3

4

5

Fig. 8: Connection, valve plug ISO 4400 with IDC crimping technology
1 Compression nut

2 Cable

3 Seal ring

4 Terminal insert

5 Plug housing

We recommend connecting VEGASWING 51 in such a way that the

switching circuit is open when there is a level signal, line break or

failure (safe condition).

Warning:

The instrument must not be operated without an intermediately

connected load, because the electronics would be destroyed if con-

nected directly to the mains. It is not suitable for connection to low

voltage PLC inputs.
Examples for typical applications:

Load resistance at 24 V DC: 88 … 1800 Ω

Rated power, relay 253 V AC: > 2.5 VA

Rated power, relay 24 V AC: > 0.5 VA

For direct control of relays, contactors, magnet valves, warning lights,

horns etc.
Domestic current is temporarily lowered below 1 mA after switching

off the load so that contactors, whose holding current is lower than

the constant domestic current of the electronics (3 mA), are reliably

switched off.