7 maintenance and fault rectification, 1 maintenance, 2 rectify faults – VEGA VEGASWING 51 - contactless electronic switch User Manual

Page 18

Advertising
background image

18

7 Maintenance and fault rectification

VEGASWING 51 • - contactless electronic switch

41045-EN-130322

7 Maintenance and fault rectification

7.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

7.2 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

VEGASWING 51 offers maximum reliability. Nevertheless, faults can

occur during operation. These may be caused by the following, e.g.:

Sensor

Process

Voltage supply

Signal processing

The first measure to be taken is to check the output signal. In many

cases, the causes can be determined this way and the faults rectified.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

Error

Cause

Rectification

Green signal

lamp off

Voltage supply in-

terrupted.

Check the voltage supply and the ca-

ble connection

Electronics de-

fective

Exchange the instrument or send it in

for repair

Red signal lamp

lights (switching

output high-im-

pedance)

Error with the

electrical con-

nection

Connect the instrument according to

the wiring plan

Shortcircuit or

overload

Check the electrical connection

Red signal lamp

flashes (switching

output high-im-

pedance)

Virbating fre-

quency out of

specification

Check the vibrating element on build-

up and remove it

Buildup on the vi-

brating element

Check the vibrating element and

the sensor if there is buildup and re-

move it

Vibrating element

damaged

Check if the vibrating element is dam-

age or extremely corroded

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

Reaction when malfunc-

tions occur

Failure reasons

Fault rectification

24 hour service hotline

Checking the switching

signal

Reaction after fault recti-

fication

Advertising