SENA UPSLink100 User Manual

Page 28

Advertising
background image

28

4.2.2 Access control configuration

Access Control defines accessibility of managers to the UPSLink SNMP agent. Only a manager from

the specified NMS can access UPSLink SNMP agent to exchange information and control actions. If

there is no specific IP address (all IP address are defaulted to 0.0.0.0), a manager from any host can

access the UPSLink SNMP agent with read-only privilege.

4.2.3 Trap receiver configuration

The trap receiver defines managers that can be notified of significant events (TRAP) from the UPSLink

SNMP agent. If there is no trap receiver, just give 0.0.0.0 for that.

SNMP traps for UPS alarms are sent as either of RFC1628 type or SENA type. The former is sent in

compliance with RFC1628 UPS MIB and the latter type of trap has an additional field to SNMP v1 trap

so that receivers could identify the cause easier. Table 0-2 shows the “specific types” field in the Sena

type of traps.

There is one more trap type ‘EASY_TRAP’. Select this type to send a Non-RFC1628 SNMP v1 trap

that is to be directly sent from UPS serial program. See ‘UPS serial programming guide’to learn more.

Specific type

Alarm description

1

One or more batteries have been determined to require replacement.

2

The UPS is drawing power from the batteries.

3

The remaining battery run-time is less than or equal to upsConfigLowBattTime.

4

The UPS will be unable to sustain the present load when and if the utility power is

lost.

5

A temperature is out of tolerance.

6

An input condition is out of tolerance.

7

An output condition (other than OutputOverload) is out of tolerance.

8

The output load exceeds the UPS output capacity.

9

The Bypass is presently engaged on the UPS.

10

The Bypass is out of tolerance.

11

The UPS has shutdown as requested, i.e., the output is off.

12

The entire UPS has shutdown as commanded.

13

An uncorrected problem has been detected within the UPS charger subsystem.

14

The output of the UPS is in the off state.

15

The UPS system is in the off state.

16

The failure of one or more fans in the UPS has been detected.

17

The failure of one or more fuses has been detected.

Advertising