Chapter 3. Breaker Operation

8

Spring Discharge Interlock

The spring discharge interlock functions in conjunction

with the circuit breaker’s draw-out interlock and a

compartment-mounted cam to discharge the closing and

opening springs before the breaker can be withdrawn

from the compartment. It includes an inverted “T” rod

beneath the circuit breaker, which has two functions.
In the DISC position, the inverted “T” rod prevents the

breaker from being further withdrawn from the

compartment until the closing and opening springs are

discharged. In the CONN position, the inverted “T” rod

aligns beneath a stop bracket in the compartment which

blocks lifting of the “T” rod and prevents the spring

discharge interlock lever from being used to close the

circuit breaker.
When the circuit breaker is racked to the DISC position,

the draw-out interlock pin is lifted by the compartment

cam. This holds the circuit breaker trip shaft & latch in a

trip-free position. The breaker cannot be closed.

Depressing the spring discharge lever releases the closing

spring energy and the mechanism crashes (closing springs

discharge but breaker does not close). Depressing the

lever also lifts the “T” rod beneath the breaker, lifting it

above the ramped interlock beneath the breaker, thus

releasing the breaker to rollout to the fully withdrawn

position.
Note: If the breaker is out of the switchgear compartment,

the spring discharge interlock will act as a closing lever

since no other interlocks will be holding the trip shaft in a

trip-free position as the closing spring energy is released.

3.4 Equipment Interlocks

Additional optional interlocks may be furnished with the

breaker enclosure. The Key Interlock prevents the breaker

from closing when the interlock is engaged and requires

one or more keys to operate. The Door Interlock prevents

opening of the enclosure door when the breaker is

in the

CONN

position. It can be defeated for authorized access.

The door can be opened by racking the breaker to the

TEST or DISC position.