EntelliGuard™ 3200–5000 Ampere Power Circuit Breakers

Chapter 1. Introduction

1

1.1 Overview

EntelliGuard™ 3200–5000 A power circuit breakers are

designed to protect low-voltage power circuits when used

with Entellisys™ Low-Voltage Switchgear.

1.2 Receiving the Breaker

Unpack the circuit breaker and inspect it for shipping

damage. Ensure that the breaker has the proper current,

voltage, and interruption ratings for the application.
The weights of the various frame sizes are listed in Table

1, for reference.

Breaker

Frame

Operation

Type

Weight

lb [kg]

3200 A

Manual

Electrical

455 [207]

470 [214]

4000 A

Manual

Electrical

560 [255]

575 [261]

5000 A

Manual

Electrical

600 [273]

615 [280]

Table 1. Weights of various breaker frame sizes.

Storage

The breaker should be placed in service immediately in its

permanent location. However, if it must be stored for an

indefinite period, it should be carefully protected against

condensation, preferably by storage in a warm dry room.
The breaker should be stored in a clean location, free

from corrosive gases or fumes. In particular, protect the

breaker from moisture and cement dust, as that combina-

tion may be corrosive.
If the breaker is stored for any length of time, it should be

inspected periodically to ensure good mechanical condi-

tion.

1.3 Preparation for Installation

Check that the primary disconnect fingers are smooth and

free of nicks and burrs. If they are dry, apply a thin coat of

GE Lubricant D6A15A1 (MobilGrease 28, catalog number

193A1751P1) to the contact surfaces.

Accessory Installation

The following accessories may be installed in the breaker

at the factory. Refer to the instruction sheet supplied with

each accessory for catalog numbers and installation

instructions.

• Shunt Trip
• Charging Motor
• Remote Close
• Open-Fuse Lockout
• Bell Alarm with Lockout
• Network Interlock
• Hidden Close Button

1.4 Breaker Features

EntelliGuard circuit breakers are equipped with the

standard and optional features illustrated in Figure 1. The

letters are keyed to the list below the figure.