7 hidden close button – GE Industrial Solutions EntelliGuard 3200–5000 A Frames, 240–600 Vac User Manual

Page 21

Advertising
background image

EntelliGuard™ 3200–5000 Ampere Power Circuit Breakers

Chapter 4. Accessory Operation

13

4.7 Hidden Close Button

The Hidden Close Button is an unmarked replacement

for the normal

CLOSE

button. A Hidden Close Button is

always provided on an EntelliGuard breaker with a

Network Interlock device. Pressing the Hidden Close

Button in the normal manner will not close the breaker.

The catalog number is WPHIDONKIT1. For installation

instructions see DEH187.

Operation

Charge the breaker closing springs, then insert the end of

a stiff rod, with maximum diameter of 0.1", through the

hole in the center of the Hidden Close Button, as illus-

trated in Figure 9. When the rod engages the mechanism,

light pressure on the rod will close the breaker

mechanism. The Hidden Close Button is double-insulated

from the current-carrying parts of the breaker.

Figure 9. Operation of the Hidden Close Button.