GE Industrial Solutions EntelliGuard 3200–5000 A Frames, 240–600 Vac User Manual

Page 18

Advertising
background image

EntelliGuard™ 3200–5000 A Power Circuit Breakers
Chapter 3. Breaker Operation

10

10 Aux Switch (NO contact)

1

Aux Switch

2

Aux Switch

11 Aux Switch (NC contact)

13

Flux Shifter

12

Flux Shifter common

5

Shunt Trip

7

Shunt Trip common

9

Close Circuit

18

Close Circuit common

8

Closing Spring Charging Motor

17

Closing Spring Charging Motor common

3

Remote Charge Indicator

4

Remote Charge Indicator

14

Bell Alarm Trip

6

Bell Alarm Trip Common

16

Bell Alarm Status

19

Bell Alarm Status Comon

OR

15

Network Interlock SET

20

Network Interlock RESET

21

Network Interlock SET/RESET common

16

Network Interlock Status

19

Network Interlock Status common

22 OFLO (phase A)
23 OFLO (phase A)

24 OFLO (phase B)
25 OFLO (phase B)

26 OFLO (phase C)
27 OFLO (phase C)

28

Spare

29

Spare

30

Spare

31

Spare

32

Spare

33

Spare

34

Spare

35

Cooling Fan

36

Cooling Fan Common

Table 3. Secondary disconnect terminals and standard connections