1 shunt trip, 2 charging motor, 3 remote close – GE Industrial Solutions EntelliGuard 3200–5000 A Frames, 240–600 Vac User Manual

Page 19: 4 open-fuse lockout

Advertising
background image

EntelliGuard™ 3200–5000 Ampere Power Circuit Breakers

Chapter 4. Accessory Operation

11

.This chapter contains the operation procedures for each

of the available breaker accessories.

4.1 Shunt Trip

The Shunt Trip allows the breaker to be opened remotely

by the EntelliGuard Messenger™. It is always provided on

electrically operated breakers. The catalog number and

current ratings for the Shunt Trip are given in Table 4.

For installation instructions see DEH169.

Catalog

Number

Voltage

Rating

WPS1LF60120 120 Vac, 60 Hz

Table 4. Catalog number and electrical rating for the Shunt Trip

accessory.

Operation

The Shunt Trip causes the circuit breaker to trip when its

coil is energized. An “A” auxiliary switch, which is closed

when the breaker is closed, is in series with the Shunt Trip

coil, as illustrated in Figure 5. The voltage source is

connected to positions 5 and 7 on the secondary

disconnect.







Figure 5. Shunt Trip connections to the auxiliary switch and secondary

disconnect.

4.2 Charging Motor

The Charging Motor provides a means of electrically

charging the springs that close the breaker. The Charging

Motor is available only as a factory-installed option. It is

always provided on electrically operated breakers.

Operation

The circuit breaker closing springs are charged automati-

cally when control voltage is applied to terminals 8 and 17

of the secondary disconnect. When the springs are fully

charged, a cutoff switch automatically de-energizes the

motor. The closing springs will recharge automatically

after the breaker closes.

4.3 Remote Close

The Remote Close allows the breaker to be closed

remotely by the EntelliGuard Messenger™ after the

closing springs have been charged. It is always provided

on electrically operated breakers. The catalog number

and operating voltage are listed in Table 5. For

installation instructions see DEH173.

Catalog Number

Voltage Rating

WPRCLF60120

120 Vac, 60 Hz

Table 5. Catalog number and electrical rating for the Remote Close

accessory.

Operation

A circuit breaker equipped with the Remote Close acces-

sory can be closed by applying the rated control voltage to

terminals 9 and 18 of the secondary disconnect.
The Remote Close accessory is continuously rated and has

an antipump feature that prevents a motor-operated

breaker from repeatedly closing if the closing signal is

maintained. The closing control voltage must be removed

for 1–2.5 seconds and then reapplied for each breaker

closure.

4.4 Open-Fuse Lockout

The Open-Fuse Lockout is used in combination with a

Fuse Rollout Element. When any fuse blows, the Open-

Fuse Lockout trips the breaker to prevent single-phasing.

This accessory is available only as a factory-installed

option.

Operation

The Open-Fuse Lockout contains an individual trip sole-

noid for each pole, connected directly across the fuse in

that phase as illustrated in Figure 6. When any fuse blows,

its solenoid is energized and trips the breaker. An

indicator shows which fuse has blown. The breaker cannot

be reclosed until the blown fuse is replaced and the

RESET button is pressed on the Open-Fuse Lockout. The

Open-Fuse Lockout connects to the fuses in a Fuse Rollout

Element through the secondary disconnect.

Figure 6. Open-Fuse Lockout (OFLO) connections to the secondary

disconnect.

5

7

Aux Switch

3C

3

2

1

Shunt Trip

22

2

1

OFLO

Phase A

23

24

4

3

OFLO

Phase B

25

26

6

5

OFLO

Phase C

27