5 bell alarm with lockout, 6 network interlock, Operation – GE Industrial Solutions EntelliGuard 3200–5000 A Frames, 240–600 Vac User Manual

Page 20

Advertising
background image

EntelliGuard™ 3200–5000 A Power Circuit Breakers
Chapter 4. Accessory Operation

12

4.5 Bell Alarm with Lockout

The Bell Alarm with Lockout prevents closing of the

breaker after a protection trip until the Bell Alarm with

Lockout is reset. It contains a set of switch contacts to

remotely indicate that the circuit breaker has tripped

because of a protection trip. Catalog numbers for the Bell

Alarm with Lockout module and kit are given in Table 6.

For installation instructions and trouble-shooting, see

DEH239.

Kit Catalog

Number

Module Catalog

Number

EGBLALMLFKIT

EGBLALMRPLC

Table 6. Catalog numbers for the Bell Alarm with Lockout Module and

Kit.

Operation

The Bell Alarm with Lockout prevents reclosing of the

breaker after a trip until it is reset. The accessory is

activated and its status circuit changes state whenever the

breaker is tripped by an overcurrent, ground fault, or

protective relay function via the EntelliGuard

Messenger™. The EntelliGuard Messenger continuously

monitors the state of the status circuit. The connections of

the Bell Alarm with Lockout to the secondary disconnect

are illustrated in Figure 7. A trip caused by the manual

OPEN button or by the Shunt Trip does not activate the

Bell Alarm with Lockout.
The Bell Alarm with Lockout can be reset by manually

depressing the yellow target/RESET button on the

breaker escutcheon. This will return the Bell Alarm with

Lockout status contact to its normal configuration and

allow the breaker to be closed.
Note: The lockout feature will only function if the circuit

breaker is racked into the CONN position.





Figure 7.

Bell

Alarm with Lockout connections to the secondary disconnect. The

contact is shown in the RESET state.




4.6 Network Interlock

The Network Interlock provides a means of locking out a

breaker to coordinate its operation with other breakers in

the distribution network. When activated by the

EntelliGuard Messenger™, the Network Interlock prevents

the breaker from closing. When the EntelliGuard

Messenger issues a RESET signal, the breaker is able to

close either remotely or locally. The Network Interlock

contains a set of switch contacts to remotely indicate the

state of the lockout and, thus, whether or not the breaker

can be closed. Catalog numbers and the operating voltage

for the Network Interlock are listed in Table 7. For

installation instructions and trouble-shooting, see

DEH41118. The Network Interlock accessory is only

available on electrically operated breakers.

Kit Catalog

Number

Module Catalog

Number

Voltage Rating

EGNTWKLFKIT

EGNTWKLFRPLC 120 Vac, 60 Hz

Table 7. Catalog numbers and control voltage for the Network

Interlock accessory.

Operation

The Network Interlock consists of a trip circuit, a reset

circuit, and a status circuit. The device connections to the

secondary disconnect are shown in Figure 8. Note that a

Bell Alarm with Lockout and a Network Interlock cannot

be installed concurrently in a breaker.







Figure 8. Network Interlock connections to the secondary disconnect.

14

2

1

Lockout

Trip Coil

6

16

4

3

Status

Contact

19

15

NI Set

Coil

20

21

NI Reset

Coil

1

3

2

16

19

4

5

NI Status

Contact

Advertising