Extension plenum - general guidelines, Extension plenum – general guidelines – GE Industrial Solutions Limitamp AR User Manual

Page 14

Advertising
background image

CR 194 One/Two-High Vacuum Limitamp

®

AR Control

Page 14

Extension Plenum – General guidelines

1. Support the Extension plenum minimum 40 inches span

throughout the straight length.

2. Straight lengths can be used along with Front/Rear

and/or Up/Down elbows to fit the customer layout.

3. Use the bottom cover plate with ø 0.635 holes for

supporting the extension plenum.

4. Optionally, Contact GE factory to order collars which

can be installed on the plenum for supporting the straight

extension plenum from the top.

5. Extension plenums are constructed using 12 gauge

sheet metal.

6. Allow minimum 76 inches straight length between turns

when designing the layout of the extension plenum.

7. Customer can install his own version of End duct or if

there is a local code requirement with a minimum exhaust

area of 428 in

2

.

8. Refer installation section to assemble extension plenums.