Introduction, Opening high voltage door, Opening high-voltage door – GE Industrial Solutions Limitamp AR User Manual

Page 3

Advertising
background image

Introduction

GE’s Limitamp

®

AR is the solution for applications where an

extra margin of protection is essential. It meets the IEEE

C37.20.7 Type 2B and IEC 62271-200, TYPE-A standards and is

available in one- and two-high versions of FVNR motor

starters, rated for 2.4-7.2kV-400A, 5kV-800A.

This instruction book is to be used in conjunction with GEH-

6263 (Two high vacuum equipment), GEH-5306 (vacuum

contactor) and GEH 5396B (800A) instructions.

WARNING: Before any adjustments, servicing, parts

replacement or any other act is performed requiring

physical contact with the electrical working components

or wiring of this equipment, all power must be removed

and locked off from all sources and all attached rotating

equipment must have come to a complete stop. User

personnel must be completely familiar with the following

operating and maintenance instructions before attempting

to service this equipment.

WARNING: The vacuum interrupter integrity test should be

performed before the high voltage vacuum contactors are

energized for the first time and each time the contactors

are returned to service after maintenance, adjustment or

repair. Failure to perform this test may result in serious

injury or death.

CAUTION: Product is not intended for nuclear use.

Opening High-Voltage Door

The high-voltage doors on the CR194 Two-High Vacuum

Limitamp AR are mechanically interlocked to prevent the

opening of the doors, when equipment is energized. For

safe opening of high-voltage door, follow the step-by-step

procedure as mentioned below.
Step 1: Push in the handle latch release and rotate the

isolation switch handle to the full “OFF” position. The latch

release must pop back out. See figure 3.
Step 2: Rotate the handle (Black color handle) down with a

rapid positive motion, to bring it to “OFF” Position.
Step 3: Rotate the high-voltage door latch handle (silver color)

90° in the counter-clockwise direction to disengage the multi

latches on the inside of the door.
Step 4: Turn all flange nuts simultaneously until disengaged

from hat brackets.
Step 5: The high-voltage door may then be opened by pulling

out on the latch handle.

Figure 3. Push in

the handle latch

WARNING: Confirm that equipment is de-energized before

opening the high-voltage doors.

CR 194 One/Two-High Vacuum Limitamp

®

AR Control

Page 3

Figure 1. 36”

wide Two-High

AR FVNR starter

with low-voltage

doors open.

Figure 2. 36”

wide Two-High

AR FVNR starter

with high-voltage

doors open.